Multi Split Cinco DCIIndoor Units Outdoor UnitsType Image ModelModelWall mountedPNX 009CINCO 100 DCIYAZ5036-H11PNX 012PNX 018PNX 021PNX 024HFD 007HFD
2-4PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3 Indoor Units Data2.3.1 PNX009 DCI SpecificationsModel Indoor Unit PNX009 DCIInstallation Method of Pipe Fl
12-23CONTROL SYSTEMSM CINCO 1-A.1 GBWater LevelANY0BLINKNLOADOPER LEDLEVEL1LEVEL2&3LEVEL4NORMALONPumpOFFOnOffOverflow signal to ODU12.6.5.2 1 Lev
12-24CONTROL SYSTEM SM CINCO 1-A.1 GB12.6.6 High/Low Pressure ProtectionWhenever high or low pressure accures in the system which extend beind
12-25CONTROL SYSTEMSM CINCO 1-A.1 GBIsInstTestCompleted=1Electrical Power UpNoEnter or ESC is pressed?Blink “it”Start Installation testPresent Normal
12-26CONTROL SYSTEM SM CINCO 1-A.1 GBHow to interpret the results (pf sub menu):Test Result (pf)InterpretationNUL The test has never been don
12-27CONTROL SYSTEMSM CINCO 1-A.1 GBExamples:12.7.10 Matrix Table Test Result (tbl)IDU channels on the DMSMPChannel1 (j=1) Channel2 (j=2) Channel3 (j
12-28CONTROL SYSTEM SM CINCO 1-A.1 GBStored Matrix Type[Rows, Column]How to present?2 x 2Repeat: r1(keep 2 sec) X1Y1 (keep 2 sec)Repeat: r2 (k
12-29CONTROL SYSTEMSM CINCO 1-A.1 GB12.9 User Interface12.9.1 User interface description o The user interface uses three 7 segments, and 4 keys.o K
12-30CONTROL SYSTEM SM CINCO 1-A.1 GB12.9.3 Menus12.9.3.1 Main Menu Notes:o The default presentation will be the mode of the unit (Cl/Ht/Sb).
12-31CONTROL SYSTEMSM CINCO 1-A.1 GBo Technician Test mode is exited after 60 minutes from entry.o All the menus, except technician menus- Status, T
12-32CONTROL SYSTEM SM CINCO 1-A.1 GB12.9.3.2 Status (Sub Menu)Status (Stt) IDU ICT ICT-A ICT-B ICT-C
2-5PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.4 PNX021 DCI SpecificationsModel Indoor Unit / TypePNX021 DCI / Wall MountedInstallation Method of pipeFLA
12-33CONTROL SYSTEMSM CINCO 1-A.1 GBNotes: For the temperature display, when a thermistor is shorted or disconnected it shows FLT (FLt), when it is
12-34CONTROL SYSTEM SM CINCO 1-A.1 GB12.10 Jumper/DIP-Switch Setting 12.10.1 Jumper/DIP-Switch Definition0 = Open (Disconnected)1 = Close (Shor
12-35CONTROL SYSTEMSM CINCO 1-A.1 GB12.10.2.6 Installation height /DIP – J12/13Installation Height designation Installation Height J13 J12H0 2.1-2.7
12-36CONTROL SYSTEM SM CINCO 1-A.1 GB12.11 System Parameters12.11.1 General Parameters for All Models# Name Default Value Units1. MinOFFTime
12-37CONTROL SYSTEMSM CINCO 1-A.1 GB# Name Default Value Units31. ICTOH4 55 °C32. ICTOH5 58 °C33. ICTOH6 61 °C34. EEVLearning 1NA35. EEVTimeSingl
12-38CONTROL SYSTEM SM CINCO 1-A.1 GB№ Name AB Unit39. EEVMultiMinOperOpenC 50 step40. EEVMultiMinOperOpenH 50 step41. EEVMinOperOpenHInacti
12-39CONTROL SYSTEMSM CINCO 1-A.1 GB12.11.3.1 Model Depended Parameters:12.11.3.1.1 Wall Mounted Models- WNGParameter nameModel25 35 50 60 72NLOAD l
12-40CONTROL SYSTEM SM CINCO 1-A.1 GB12.11.3.1.3 Wall Mounted Models- TopParameter nameModel25 35NLOAD limits as a function of selected indoor
12-41CONTROL SYSTEMSM CINCO 1-A.1 GB12.11.3.1.5 Cassettes Models - CNParameter nameModel25 35 50 60 72NLOAD limits as a function of selected indoor f
13-1TROUBLESHOOTINGSM CINCO 1-A.1 GB13. TROUBLESHOOTING13.1 Precaution, Advise and Notice Items13.1.1 High voltage in Indoor and Outdoor unit electr
2-6PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.7 HFD009 DCI Specifications Model Indoor Unit HFD009 DCIInstallation Method of Pipe FlaredPower supply V/Ph
13-2TROUBLESHOOTING SM CINCO 1-A.1 GB13.2 General System Failures and Corrective Actions№ SYMPTOM / PROBLEM PROBABLE CAUSE CORRECTIVE ACTIONIn
13-3TROUBLESHOOTINGSM CINCO 1-A.1 GB№ SYMPTOM / PROBLEM PROBABLE CAUSE CORRECTIVE ACTION11 Compressor does not start operationOne or some components a
13-4TROUBLESHOOTING SM CINCO 1-A.1 GB№ SYMPTOM / PROBLEM PROBABLE CAUSE CORRECTIVE ACTION18 Compressor is generating abnormal noisePhase order
13-5TROUBLESHOOTINGSM CINCO 1-A.1 GB№Problem AO 543211 OCT is shorted/disconnected Yes 000012 CTT is shorted/disconnected Yes 000103 HST is shorted/di
13-6TROUBLESHOOTING SM CINCO 1-A.1 GB13.4.2 Outdoor unit diagnostics and corrective actions№ Fault Name Fault Description Corrective Action1 O
13-7TROUBLESHOOTINGSM CINCO 1-A.1 GB№ Fault Name Fault Description Corrective Action22 Compressor Over Heating Compressor stopped due to over heat pro
13-8TROUBLESHOOTING SM CINCO 1-A.1 GBChannel LEDRi has communication The relevant LEDi will be ON.Ri has no communication The relevant LEDi wil
13-9TROUBLESHOOTINGSM CINCO 1-A.1 GB№ Fault Name 5 4 3 2 127 Using EEPROM data 1 1 0 1 128 Model A 1 1 1 0 029 Model B 1 1 1 0 130 Model C 1 1 1 1 03
13-10TROUBLESHOOTING SM CINCO 1-A.1 GB13.5 Procedures for checking Main Parts13.5.1 Discharge DC Voltage 13.5.2 Checking Mains Voltage Confi
13-11TROUBLESHOOTINGSM CINCO 1-A.1 GB13.5.7 Checking Outdoor Fan MotorThis type of fault may occur during very high winds outdoors that may stop the
2-7PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.10 HAD007 DCI Specifications Model Indoor Unit / Type HAD007 DCI / Wall MountedInstallation Method of pipe
13-12TROUBLESHOOTING SM CINCO 1-A.1 GB13.5.8 Checking CompressorCheck Compressor connections - Repair if needed.1) Check the resistance between
13-13TROUBLESHOOTINGSM CINCO 1-A.1 GBOAT, OCT, OMT, ICT, RAT, RGT, RLT, HST ChartCTT ChartReplacing thermistor - (14.1.12.)Replacing main board - (14.
13-14TROUBLESHOOTING SM CINCO 1-A.1 GB13.5.12 Checking High Pressure Switch (HPS)Disconnect HPS connector from the main board and check resist
13-15TROUBLESHOOTINGSM CINCO 1-A.1 GB13.5.18.2 EMC interference to near by home appliances Locations most susceptible to interference:A television or
14-1SERVICINGSM CINCO 1-A.1 GB14. SERVICINGNote: To reassemble perform the procedures in reverse.14.1 Removing Service (front) panel Remove the fixin
14-2SERVICINGSM CINCO 1-A.1 GB14.5 Removing Air Outlet Grille(s) Remove the fixing screws of the each grille. 14.6 Removing Outdoor Fan Remove the a
14-3SERVICINGSM CINCO 1-A.1 GB14.8 Removing Reversing Valve coil Remove the service front panel according to 1. 14.1.Check to ensure that LEDs and
14-4SERVICINGSM CINCO 1-A.1 GBRemove the nuts fixing the compressor and lift the compressor.NOTES for re-assembling new compressor:To1. prevent cont
14-5SERVICINGSM CINCO 1-A.1 GB14.13 Removing main boards Remove the service panels according 1. to 14.1 and 14.2.Check to ensure that LEDs and disp
14-6SERVICINGSM CINCO 1-A.1 GB14.15 Removing driver module Remove the electrical assembly according 1. to 14.14.Remove the screws fixing the main bo
2-8PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.13 HAD021 DCI Specifications Model Indoor Unit / TypeHAD021 DCI / Wall MountedInstallation Method of pipe
15-1EXPLODED VIEWS AND SPARE PARTS LISTSSM CINCO 1-A.1 GB15. EXPLODED VIEWS AND SPARE PARTS LISTS15.1 Outdoor Unit: Cinco 100 DCI12a 12b1312 12c1273
15-2EXPLODED VIEWS AND SPARE PARTS LISTSSM CINCO 1-A.1 GB15.2 Outdoor Unit: Cinco 100 DCI16334343b43a14702137403850b50c50d3969494949494950a50e3175654
15-3EXPLODED VIEWS AND SPARE PARTS LISTSSM CINCO 1-A.1 GB15.3 Outdoor Unit: CINCO 100 DCI => SPARE PART LISTSP No. Item Description Quantity1 4370
OPTIONAL ACCESSORIES16-1SM CINCO 1-A.1 GB16. OPTIONAL ACCESSORIES16.1 RCW Wall Mounted Remote Control 16.1.1 The RCW wall mounted remote control can
OPTIONAL ACCESSORIES16-2 SM CINCO 1-A.1 GB16.2 RCW2 Wall Mounted Remote Control16.2.1 The RCW2 wall mounted remote controler is a wired controler th
OPTIONAL ACCESSORIES16-3SM CINCO 1-A.1 GB16.3 Base HeaterPN: 439878Before starting the heaters connection verify that the unit is disconnected from ma
OPTIONAL ACCESSORIES16-4 SM CINCO 1-A.1 GB16.4 Crank Case HeaterPN: 190443Before starting the heaters connection verify that the unit is disconnecte
OPTIONAL ACCESSORIES16-5SM CINCO 1-A.1 GB16.5 Room Thermostat Room Thermostat kit PN: 442298Thermistor with connector PN: 442296Before starting the co
17-1APPENDIX ASM CINCO 1-A.1 GBAPPENDIX AINSTALLATION AND OPERATION MANUAL► INSTALLATION MANUAL CINCO 100 DCI
2-9PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.16 XLF012 DCI Specifications Model Indoor Unit XLF012 DCIInstallation Method of Pipe FlaredPower supply V/P
2-10PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.19 CK018 DCI Specifications Model Indoor Unit CK018 DCIInstallation Method of Pipe FlaredPower supply V/Ph
2-11PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.22 SX009 DCI SpecificationsModel Indoor Unit SX009 DCI Installation Method of Pipe FlaredPower supply V/Ph
2-12PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.25 SX021 DCI Specifications Model Indoor Unit / TypeSX012 DCI / Floor-CeilingInstallation Method of pipe F
2-13PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.28 DLF012 DCI Specifications Model Indoor Unit DLF012 DCI Installation Method of Pipe DUCTEDPower supply V
ALIST OF EFFECTIVE PAGESSM CINCO 1-A.1 GBLIST OF EFFECTIVE PAGESNote: Changes in the pages are indicated by a “Revision#” in the footer of each effec
2-14PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.31 DLF024 DCI SpecificationsModel Indoor Unit / TypeDLF024 DCI / Low SilouhetteInstallation Method of pipe
2-15PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.3.34 DLS024 DCI Specifications Model Indoor Unit / TypeDLS024 DCI / DuctedInstallation Method of pipe FLARE
3-1RATING CONDITIONS SM CINCO 1-A.1 GB3. RATING CONDITIONSStandard conditions in accordance with ISO 5151, ISO 13253 (
4-1OUTLINE DIMENSIONSSM CINCO 1-A.1 GB4. OUTLINE DIMENSIONS4.1 Indoor Unit: PNX009 / PNX012 DCI4.2 Indoor Unit: PNX018 / PNX021 / PNX024 DCI10602212
4-2OUTLINE DIMENSIONS SM CINCO 1-A.1 GB4.3 Indoor Units: HFD007 / HFD009 DCI4.4 Indoor Unit: HFD012 DCI
4-3OUTLINE DIMENSIONSSM CINCO 1-A.1 GB4.5 Indoor Unit: HFD018 DCI4.6 Indoor Unit: HAD007 / HAD009 DCI900295AIR INTAKEAIR INTAKEAIR OUTLET205MOUNTING
4-4OUTLINE DIMENSIONS SM CINCO 1-A.1 GB4.7 Indoor Units: HAD012 DCI4.8 Indoor Units: HAD018 / HAD021 / HAD024 DCI1882508361060219295
4-5OUTLINE DIMENSIONSSM CINCO 1-A.1 GB4.9 Indoor Unit: XLF009 / XLF012 DCI4.10 Indoor Unit: CK009 / CK012 / CK018 / CK021 / CK024 DCIUnit Model Main
4-6OUTLINE DIMENSIONS SM CINCO 1-A.1 GBAC565B629 (640 With air filter)59212002716059Nominal Capacity A B C2.5 -5.0 kW 750 696 7906.0-7.2 kW 105
4-7OUTLINE DIMENSIONSSM CINCO 1-A.1 GBJIFADE359B198073GKLHC36614.13 Indoor Unit: DLS018 / DLS021 / DLS024 DCIModel A B C D E F G H I J K LDLS018 / DL
iTABLE OF CONTENTSSM CINCO 1-A.1 GBTable of Contents1. INTRODUCTION ...
5-1PERFORMANCE DATASM CINCO 1-A.1 GB5. PERFORMANCE DATA5.1 Outdoor Unit Cinco 100 DCI Combinations (Delta + LEX)5.1.1 CoolingModelCooling Capacity [
5-2PERFORMANCE DATA SM CINCO 1-A.1 GBModelCooling Capacity [KW]Power Consumption [kW]EERA B C D E Nom. Min. Max. Nom. Min. Max. Nom.9+12+12 2.
5-3PERFORMANCE DATASM CINCO 1-A.1 GBModelCooling Capacity [KW]Power Consumption [kW]EERA B C D E Nom. Min. Max. Nom. Min. Max. Nom.7+7+7+7+12 1.7 1.7
5-4PERFORMANCE DATA SM CINCO 1-A.1 GB5.1.2 HeatingModelHeating Capacity [KW]Power Consumption [kW]COPA B C D E Nom. Min. Max. Nom. Min. Max. N
5-5PERFORMANCE DATASM CINCO 1-A.1 GBModelHeating Capacity [KW]Power Consumption [kW]COPA B C D E Nom. Min. Max. Nom. Min. Max. Nom.9+18+21 2.0 - - 3.9
5-6PERFORMANCE DATA SM CINCO 1-A.1 GBModelHeating Capacity [KW]Power Consumption [kW]COPA B C D E Nom. Min. Max. Nom. Min. Max. Nom.7+7+7+9+18
5-7PERFORMANCE DATASM CINCO 1-A.1 GB5.2 LEX 25 DCI5.2.1 Cooling Capacity Factors - Unit A, B, C, D or E230[V] : Indoor Fan at High Speed. OD COIL
5-8PERFORMANCE DATA SM CINCO 1-A.1 GB5.2.3 Heating Capacity Factors - Unit A, B, C, D or E230[V] : Indoor Fan at High Speed. OD COIL ENTERI
5-9PERFORMANCE DATASM CINCO 1-A.1 GB5.3 LEX 35 DCI5.3.1 Cooling Capacity Factors - Unit A, B, C, D or E230[V] : Indoor Fan at High Speed.OD COIL ENT
5-10PERFORMANCE DATA SM CINCO 1-A.1 GB5.3.3 Heating Capacity Factors - Unit A, B, C, D or E230[V] : Indoor Fan at High Speed. OD COIL ENTER
1-1INTRODUCTIONSM CINCO 1-A.1 GB1. INTRODUCTION1.1 GeneralThe Cinco DCI Multi is a total Multi System in one unit: Duo/Trio/Quattro/Cinco.The multi-sp
5-11PERFORMANCE DATASM CINCO 1-A.1 GB5.4 LEX 50 DCI5.4.1 Cooling Capacity Factors - Unit D or E230[V] : Indoor Fan at High Speed. OD COIL ENTERING
5-12PERFORMANCE DATA SM CINCO 1-A.1 GB5.4.3 Heating Capacity Factors - Unit D or E230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR D
5-13PERFORMANCE DATASM CINCO 1-A.1 GB5.5 LEX 60 DCI5.5.1 Cooling Capacity Factors - Unit D or E230[V] : Indoor Fan at High Speed. OD COIL ENTERING
5-14PERFORMANCE DATA SM CINCO 1-A.1 GB5.5.3 Heating Capacity Factors - Unit D or E230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR D
5-15PERFORMANCE DATASM CINCO 1-A.1 GB5.6 LEX 70 DCI5.6.1 Cooling Capacity Factors - Unit D or E230[V] : Indoor Fan at High Speed. OD COIL ENTERING
5-16PERFORMANCE DATA SM CINCO 1-A.1 GB5.6.3 Heating Capacity Factors - Unit D or E230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR D
5-17PERFORMANCE DATASM CINCO 1-A.1 GB5.7 CN 25 DCI 5.7.1 Cooling Capacity Factors - Unit A,B,C, D or E230[V] : Indoor Fan at High Speed.OD COIL ENTE
5-18PERFORMANCE DATA SM CINCO 1-A.1 GB5.7.3 Heating Capacity Factors - Unit A, B ,C, D or E 230[V] : Indoor Fan at High Speed.OD COIL ENTERI
5-19PERFORMANCE DATASM CINCO 1-A.1 GB5.8 CN 35 DCI 5.7.1 Cooling Capacity Factors - Run Mode Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed
5-20PERFORMANCE DATA SM CINCO 1-A.1 GB5.7.3 Heating Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High SpeedOD COIL ENTERIN
1-2INTRODUCTIONSM CINCO 1-A.1 GB1.4 Inbox Documentation Outdoor unit is supplied with its installation manual and flare type adaptor connectors. E
5-21PERFORMANCE DATASM CINCO 1-A.1 GB5.9 CN 50 DCI 5.9.1 Cooling Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed.OD COIL ENTERING A
5-22PERFORMANCE DATA SM CINCO 1-A.1 GB5.9.3 Heating Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed.OD COIL ENTERING AIR DB/
5-23PERFORMANCE DATASM CINCO 1-A.1 GB5.10 CN 60 DCI 5.10.1 Cooling Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed.OD COIL ENTERING
5-24PERFORMANCE DATA SM CINCO 1-A.1 GB5.10.3 Heating Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed.OD COIL ENTERING AIR DB
5-25PERFORMANCE DATASM CINCO 1-A.1 GB5.11 CN 70 DCI 5.11.1 Cooling Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed.OD COIL ENTERING
5-26PERFORMANCE DATA SM CINCO 1-A.1 GB5.11.3 Heating Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed.wOD COIL ENTERING AIR D
5-27PERFORMANCE DATASM CINCO 1-A.1 GB5.12 PXD 25 DCI 5.12.1 Cooling Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. O
5-28PERFORMANCE DATA SM CINCO 1-A.1 GB5.12.3 Heating Capacity Factor - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed.OD COIL ENTERI
5-29PERFORMANCE DATASM CINCO 1-A.1 GB5.13 PXD 35 DCI 5.13.1 Cooling Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. O
5-30PERFORMANCE DATA SM CINCO 1-A.1 GB5.13.3 Heating Capacity Factors - Unit A, B, C, D or E 230[V] : Indoor Fan at High Speed. OD COIL EN
1-3INTRODUCTIONSM CINCO 1-A.1 GB1.6 Indoor Unit combinationsDuo Trio Quattro CincoUnit DUnit EUnit A/B/CUnit DUnit EUnit A/BUnit CUnit DUnit EUnit AU
5-31PERFORMANCE DATASM CINCO 1-A.1 GB5.14 PXD 50 DCI 5.14.1 Cooling Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTE
5-32PERFORMANCE DATA SM CINCO 1-A.1 GB5.14.3 Heating Capacity Factor - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AIR
5-33PERFORMANCE DATASM CINCO 1-A.1 GB5.15 PXD 60 DCI 5.15.1 Cooling Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL EN
5-34PERFORMANCE DATA SM CINCO 1-A.1 GB5.15.3 Heating Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AI
5-35PERFORMANCE DATASM CINCO 1-A.1 GB5.16 PXD 70 DCI 5.16.1 Cooling Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL EN
5-36PERFORMANCE DATA SM CINCO 1-A.1 GB5.16.3 Heating Capacity Factors - Unit D or E 230[V] : Indoor Fan at High Speed. OD COIL ENTERING AI
5-37PERFORMANCE DATASM CINCO 1-A.1 GBTubing Length Capacity Ratio - Cooling (1 Unit)0.760.810.860.910.961.011.060 5 10 15 20 25 30Tubing Length [m]Cap
5-38PERFORMANCE DATA SM CINCO 1-A.1 GB5.18 Model Correction Factors (FM)ModelCapacity Power inputCooling Heating Cooling HeatingLEX DCI INV 1
6-1PRESSURE CURVESSM CINCO 1-A.1 GB6. OPERATING CURVES6.1 Cooling – Technician Mode Suction Pressure - Cooling (Technician Mode) (5xLEX009 ; 5m each)
6-2PRESSURE CURVESSM CINCO 1-A.1 GB6.2 Heating – Technician Mode Suction Pressure - Heating (Technician Mode) (5xLEX009 ; 5m each)3.004.005.006.007.0
2-1PRODUCT DATA SHEETSM CINCO 1-A.1 GB2. PRODUCT DATA SHEET2.1 Outdoor Unit Specifications.Model Cinco 100 DCI / YAZ5036-H11Operation Mode Cooling
6-3PRESSURE CURVESSM CINCO 1-A.1 GB6.3 Tubing Length correction Factor6.4 Outdoor Unit Code correction Factor (FC)ODU CodeCooling HeatingSuction Pre
6-4PRESSURE CURVESSM CINCO 1-A.1 GB6.5 Calculation ExampleOutdoor UnitCinco DCIIndoor CombinationLEX009+LEX009+LEX009+CK009+LEX018Operation ModeCoolin
7-1SOUND LEVEL CHARACTERISTICSSM CINCO 1-A.1 GB7. SOUND LEVEL CHARACTERISTICS7.1 Outdoor Units7.2 Sound Pressure Level Spectrum (Measured as Figure
8-1ELECTRICAL DATASM CINCO 1-A.1 GB8. ELECTRICAL DATA8.1 Cinco 100 DCIPower Supply 1 PH, 220-240 VAC, 50HzConnected to OutdoorMaximum Current 25 AIn
9-1WIRING DIAGRAMS & ELECTRICAL CONNECTIONSSM CINCO 1-A.1 GB9. WIRING DIAGRAMS & ELECTRICAL CONNECTIONS9.1 Outdoor Units: CINCO 100 DCIDANGE
9-2WIRING DIAGRAMS & ELECTRICAL CONNECTIONSService Manual - Trio_Quttro DCI9.2 1PH UNIT POWER SUPPLY TO OUTDOORLNC LNC LNC LNCCLNN1L1(Caseette)In
10-1REFRIGERATION DIAGRAMSSM CINCO 1-A.1 GB10. REFRIGERATION DIAGRAMS10.1 CINCO 100 DCI Outdoor Unit Refrigerant System DiagramMMMMMPPRefrigerant fl
11-1TUBING CONNECTIONSSM CINCO 1-A.1 GB11. TUBING CONNECTIONS TUBE (Inch)TORQUE (Nm)¼” ⅜”½”⅝”¾”Flare Nuts 11-13 40-45 60-65 70-75 80-85Valve Cap
12-1CONTROL SYSTEMSM CINCO 1-A.1 GB12. CONTROL SYSTEM12.1 AbbreviationsAbbreviation DefinitionA/C Air Conditioner BMS Building Management SystemCCR C
12-2CONTROL SYSTEM SM CINCO 1-A.1 GB12.2 Product Overview12.2.1 Block Diagram ODU Controller Line Filter 230VAC Compressor Driver M Driver Co
2-2PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.2 Outdoor Unit Capacity2.2.1 Cinco (HAD)ModelODU Cinco 100 DCI / YAZ5036-H11IDU HAD 22+ HAD 22+ HAD 22 + HAD
12-3CONTROL SYSTEMSM CINCO 1-A.1 GB12.2.2 Controller overview12.2.2.1 Main Controller Outdoor Unit Power Supply + Ground IDU-ODU Comm. Inrush / DMSM
12-4CONTROL SYSTEM SM CINCO 1-A.1 GB12.2.3 Control Features12.2.3.1 CompressorDC brush less and sensor less motor inverter driven compressor. 1
12-5CONTROL SYSTEMSM CINCO 1-A.1 GB12.2.3.9 Base HeaterHeating element designed to melt any ice that is accumulated on the outdoor unit base during lo
12-6CONTROL SYSTEM SM CINCO 1-A.1 GB12.3.2 Communication with Indoor Unit 12.3.2.1 Communication Failures Definition12.3.2.1.1 ‘Bad Communic
12-7CONTROL SYSTEMSM CINCO 1-A.1 GBThe following combinations show the allowed and not allowed capacity group:ODU Model Communication channelIs it all
12-8CONTROL SYSTEM SM CINCO 1-A.1 GB12.3.5.2 The following thermistor faults are detected by the system:Thermistor Thermistor is Disconnected
12-9CONTROL SYSTEMSM CINCO 1-A.1 GB12.4.2.2 Indoor fan control - Cool Mode When T/H/M/L speed is set by user, IFAN will work in constant requested
12-10CONTROL SYSTEM SM CINCO 1-A.1 GB12.4.3 Cooling Mode12.4.3.1 Cooling Mode – Generala. Mode DefinitionMode: COOL, AUTO (at Cooling)Temp:
12-11CONTROL SYSTEMSM CINCO 1-A.1 GB12.4.4 Heating Mode12.4.4.1 Heating - Generala. Mode DefinitionMode: HEAT, AUTO (at heating)Temp: Selected desire
12-12CONTROL SYSTEM SM CINCO 1-A.1 GB12.4.4.4 Temperature CompensationA compensation value of 2-4 degrees is reduced from room temperature read
2-3PRODUCT DATA SHEETSM CINCO 1-A.1 GB2.2.5 Duo (LEX 50)ModelODU Duo 100 DCI / YAZ5036-H11IDU LEX 50 +LEX 50Operation Mode Cooling HeatingCapacity (2
12-13CONTROL SYSTEMSM CINCO 1-A.1 GB12.4.6 Dry Mode12.4.6.1 DRY - Generala. Mode DefinitionMode: DRYTemp: Selected desired temperatureFan: LOW (aut
12-14CONTROL SYSTEM SM CINCO 1-A.1 GB12.4.7 Sleep Mode12.4.7.1 Sleep Mode - Generala. Mode DefinitionMode: AnyTemp: Selected desired temperat
12-15CONTROL SYSTEMSM CINCO 1-A.1 GB12.4.9 Indoor Units Operation when Indoor Unit Mode is Different than Outdoor Unit Mode Open louvers according
12-16CONTROL SYSTEM SM CINCO 1-A.1 GBSTBY Cool Heat Auto Fan DryOFF SPT SPT SPT SPT SPTOFF ON ON ON ON ONOFF OFF OFF OFF OFF OFF (Low
12-17CONTROL SYSTEMSM CINCO 1-A.1 GB12.5 Run ModeRun mode is the default operation mode of the system. This is the standard operation mode that is act
12-18CONTROL SYSTEM SM CINCO 1-A.1 GB12.5.2.1 Compressor Min On/Off timeCompressor minimum ON and OFF time is 3 minutes except during protecti
12-19CONTROL SYSTEMSM CINCO 1-A.1 GBODUCodeH setting:-15 -5 15ODUCodeHOAT2 2421ABCDEPoint (Set by the graph above) ODUCodeHA 2.0B 2.5C (or OAT faulty
12-20CONTROL SYSTEM SM CINCO 1-A.1 GB12.5.3.6 EEV correction definitionThe following table describes the closed loop control type (EEV correcti
12-21CONTROL SYSTEMSM CINCO 1-A.1 GB12.6.2 IDU ProtectionsICT Value ICT TrendIndoor Coil Defrost ProtectionIndoor Coil Over Heating ProtectionFast Inc
12-22CONTROL SYSTEM SM CINCO 1-A.1 GB12.6.4.2 Deicing Protection ProcedureCOMPRVOFANEEVONHEATCOOLONOFF EEVDeicerOpenAnyT1 T2T3 T3T1120